Home Inspection Report
Client(s): John Doe
Property address: 12345 Main Street
Springfield, MO 65801
Inspection date: August 12, 2007
This report published on 8/13/2007 9:49:24 PM CST

Thank you for using Marc Ekhause 'Certified' Home Inspections L.L.C. for your inspection needs. I appreciate your business.

The following written report is prepared for the sole, confidential and exclusive use of the client(s) named above. It is designed to highlight significant visual defects uncovered on the day of the inspection. It is intended as a general guide to help you evaluate the home. Read your entire Home Inspection Report before purchasing the property, paying close attention to all items noted on the report and to any exclusions and limitations listed. Any items noted that require further evaluation by a professional should be investigated before you purchase the home. I recommend that all repairs be made by a licensed, qualified contractor.

Best Wishes,

Marc Ekhause
Marc Ekhause 'Certified' Home Inspections L.L.C.


How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and shown in bold type. Items of concern follow descriptive information and are shown as follows:
SafetyPoses a risk of injury or death. Have the appropriate contractor evaluate and correct the defect at once. 
Major defectCorrection may involve a significant expense. Have the appropriate contractor evaluate and repair / replace as needed. 
Repair/ReplaceRecommend repairing or replacing. Have the appropriate contractor evaluate and repair / replace as needed. 
Minor defectDefect appears cosmetic or likely involves only a minor expense. Have it repaired or corrected at your discretion. 
MaintainMaintenance or on-going maintenance and repair needed. 
EvaluateRecommend further evaluation by licensed contractor or specialist before purchasing the home. Make any repairs based on their evaluation. 
MonitorRecommend monitoring over time, have appropriate contractor repair or replace as needed. 
CommentFor your information. 
Concern items are sorted by the types listed above.  Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Wood Destroying Organisms
Exterior
Roof Gutters Chimneys
Attached Garage
Basement or Lower Level
Crawl Space
Electric Service
Heating and Air Conditioning
Well
Water Heater
Plumbing and Laundry
Fireplaces and Woodstoves
Basement Bathroom
Hallway Bathroom
Master Bathroom
Kitchen and Interior Rooms
Attic


General Information Return to table of contents  
Start time: 8:10AM
End time: 1:15PM
Inspection fee: $599
Present during the inspection: Buyer(s), Septic company, Realtor(s), Oil / Heating Company
Was building occupied at the time of inspection: Yes
Past weather conditions possibly affecting the inspection: Very dry, hot
Weather conditions at start of inspection: Clear
Overnight temperature prior to inspection: 73 degrees
Approximate temperature at start of inspection: 85 degrees
Ground condition: Dry
Main entrance faces: South
Estimated age of building: Built in 1975
Type of building, as reported by Realtor and/or client: Single family
Number of living units found: 1
Foundation type: Basement (portions finished)
Building style: Raised Ranch
General construction material: Wood
Stories: 2 Story
1) Overall condition of the house is good - house is structurally sound. Your biggest expense will be to upgrade and repair the windows. Read entire report for details.
 


Wood Destroying Organisms Return to table of contents  
Apparent evidence of wood destroying insects found: No visible evidence found
Conductive conditions found for wood destroying insects or organisms: Wood to ground contact found at porch(s), needs correction
Major areas of rot or damage from wood destroying organisms found: None noted
2) Found wood to ground contact conductive to insects and wood rot. The support posts for the rear porch sit in the ground, allowing insects access to the framing. Posts should sit on a concrete footing. Recommend correction, call carpenter for repair.
 


Exterior Return to table of contents  
Foundation materials: Poured in place concrete
Amount of foundation wall exposed and able to be inspected: Most of foundation at least several inches exposed
Siding / wall covering: Vinyl / plastic
Exterior walls appear to be generally: Straight
Trim materials (includes eaves, soffits, fascias, window and door trim): Vinyl
Exterior door(s) appear to be made of: Wood
Number of doors exiting home: 3
Storm doors noted on exterior doors?: Yes
Sidewalk and walkway material: Poured in place concrete, Paving stones, Appears serviceable, no significant defects other than normal wear and tear
Front stoop or porch made of: Concrete
Appropriate guard rails noted on exterior steps: Guard rails not adequate, needs repair or correction
Rear or side stoop / porch made of: Wood
Roof over rear porch: Wood
Rear porch roof support columns made of: Wood
Retaining walls: None noted other than garden border type
Fences made of: Wood
Fences felt: Mostly secure
Grading at front: Toward the home
Grading at left: Away from the home
Grading at right: Away
Grading at rear: Away
Drainage on lot appears to be: Fair, some water drains away and some will drain toward the structure. Possibility of water penetration to the home exists. Correct the grading as needed.
Trees, shrubs and plantings need to be cut back or pruned from structure: Plants close to or growing on home need to be cut back
Driveway location: Front right
Driveway material: Asphalt
Carport - number of bays noted: None noted
Deck is made of: Wood
Steps or access to yard noted from deck: 15 steps
Appropriate guard rails noted on exterior steps: Guard rails not adequate, needs repair or correction
Flashing seen between deck and house: Yes
Bolts noted securing deck ledger to home: Yes
Joist hangars noted under deck: Yes
Support columns under deck made of: Wood
Patio location: Under deck at rear
Patio made of: Concrete
Storm or screen windows noted from exterior: Storm windows, Screen windows
From exterior at the ground level some windows appear to be: Uninsulated single pane
Window wells made of: None noted
Number of hose bibbs (exterior faucets) noted: 2
Brand name on compressor: Trane
Apparent age of cooling compressor: Appears brand new
3) Guardrails at rear porch missing and need to be closed down, need to correct for safety.

Photo 9  
Add and close down rail openings here for safety.
 
4) Ground Fault Circuit interrupt (GFCI) outlets not noted at exterior rear of house. GFCI outlets provide a measure of shock protection in wet or exterior areas. Needs to be corrected for safety. Recommend having a licensed electrician install outlets as necessary.

Photo 10  
 
5) Noted dry grass over the septic fields at the rear of the home. This usually means that the piping has too much gravel on top of it and not enough earth to retain moisture. Not a mechanical concern, but the grass will tend to dry out unless you add more soil on top. Add soil to yard as needed to prevent the grass from drying out.

Photo 8  
Dry soil over septic system - outline of trench pipe visible at left.
 
6) The soil or grading appears to be pitched toward the house or is level in one or more locations. This may lead to water in the basement or crawlspace areas. Soil should always be pitched AWAY from house to prevent water penetration. Monitor any areas of the basement where the soil is level or pitched against house for possible water penetration, Make sure gutters are clean and working properly, extensions should be in place on downspouts so water drains away from the house foundation. Have landscape contractor change the pitch at areas so water flows away from the structure as needed.
7) Driveway is cracked and poses a trip hazard. Recommend having a qualified paving contractor repair the driveway.

Photo 15  
 
8) Windows appear to be the older non-insulated type. Replace in the future for energy efficiency and ease of use. Two windows noted with broken glass, needs repair or replacement.

Photo 16  
 
9) Hose bibb(s) do not operate. They may be broken, disconnected or shut-off at the interior. Check with owner to see if they have been shut-off and have a plumber make any needed repairs.
10) Minor cracks and deterioration present in foundation. These are not a structural concern, but recommend sealing them to prevent water and insect infiltration.
11) Gaps and cracks were noted in the house siding. Should be caulked. Have these repaired to avoid water and insect penetration.
12) Weatherstrip at the front door is missing. Recommend installing weatherstripping at exterior door(s) where needed.
13) One or more storm doors do not operate correctly and need adjustment or repair. Closer arm missing on front door.

Photo 13  
Closer missing - front storm door.
 
14) Noted mold mildew on the interior of the rear porch, needs cleaning.

Photo 28  
 
15) Cooling compressor at exterior is not level and needs to be adjusted for proper operation of the cooling system. Mulch or shrubs block airflow to cooling compressor at exterior, needs correction.
16) Vegetation (trees, shrubs and/or vines) are too close to or are in contact with building exterior. Recommend pruning or removing vegetation as necessary so there's at least a one foot gap between all vegetation and the building exterior. This gap should exist to allow exterior building materials to dry quickly after it rains, and to eliminate pathways to the structure for wood destroying insects. Tree limbs should be pruned so that they do not overhang or touch the house. Falling limbs will damage the roof while falling leaves clog the gutters and may cause water to fall close to the foundation and seep into the basement area.
17) The finish on the deck and / or railings is worn or deteriorated. Recommend cleaning and repainting / re-staining deck.
18) The exterior door at the garage could not be opened - locked with a key, no key found to operate. Ask the owner for the key. If not available call locksmith to open.

Photo 5  
 
 


Roof Gutters Chimneys Return to table of contents  
Roof inspection method: Traversed
Roof type(s): Gable
Number of apparent roofing layers: Appears to be two or more layers of roofing material. Roof will need a "tear-down" or removal of the old roofing materials and flashings when new roof is installed.
Roof covering: Asphalt shingles, Appears serviceable, no significant defects other than normal wear and tear.
Apparent stage of life for roof: Age appears to be mid-life
Roof conditions noted: Roof appears clean, Roofing appears flat and smooth, Fresh color noted, Square shingle tab corners noted
Roof ventilation seen from exterior: Gable Vent(s), Appears serviceable, no significant defects other than normal wear and tear
Roof penetrations noted and flashings: Vent pipes, Roof Vents, Aluminum flashing
Gutter & downspout material: Aluminum
Gutters / downspouts discharge to: Pipe buried in ground, could not determine where pipe exits
Number of skylights noted from exterior: 2
Number of chimneys noted from exterior: 1
Chimney location(s): Exterior of structure
Chimney(s) made of: Brick
Flue liner noted at top of chimney: Yes
Condition of chimney(s): Cracks noted in bricks and / or mortar, Broken or cracked wash, Spark arrestor / rain cap missing
Location of chimney cleanout, if any: Boiler room, basement
Condition of cleanout door(s): Appears serviceable, no major defects noted at time of inspection
19) Downspout leader buried in ground is broken and needs repair.

Photo 11  
 
20) Noted loose bricks at chimney at ground level. Noted cracks in chimney wash (cement covering top apron of chimney) at roof level. Call mason for repair. Noted no rain cap / spark arrestor at top of chimney, call chimney service and have one added to keep rain out of the chimney and to prevent sparks from landing on roof when you light a fire.

Photo 3  
Cracks in chimney wash, top of chimney.

Photo 12  
Loose mortar.
21) Small amounts of mildew noted on roof, clean as needed.

Photo 1  
 
22) Patching noted at roof penetration at chimney, will need periodic maintenance to prevent water infiltration. It dries out and cracks over time. Maintain and repair as needed to seal any cracks or deterioration in the patching material.

Photo 2  
 
23) This asphalt or fiberglass composition roof appears to have two or more layers of roofing materials. When this roof is replaced, a complete "tear off" will be needed where all existing layers of roofing are removed before installing new roofing materials. Removing existing roofing materials will significantly increase the cost of the next roof.

Photo 4  
Roof in good condition. Multiple layers noted.
 
 


Attached Garage Return to table of contents  
Garage Floor: Concrete
Garage walls on the interior made of: Sheetrock
Observed overhead in garage: Closed in ceiling
Number of non-auto doors (to house or exterior): 2
Number of auto doors: 2
Operated garage auto door(s): In working condition
Electric openers noted: Yes
Are garage auto door safety devices installed and working: No, one or more of the safety devices are not installed or do not operate correctly, need to repair or install
Garage windows: Wood
Random tested a sampling of windows and found: Some windows do not open or close under normal pressure
Evidence of water penetration noted: Rust seen on bottoms of door hardware, indicates water penetration in the past. Need to monitor, correct as needed
24) Holes in walls and/or ceilings noted that need repair. Keep the garage envelope intact to retard flames and keep them from spreading into main structure should there be a fire.

Photo 7  
Repair openings for safety. Need to add fire-rated sheetrock here.
 
25) The garage-house door poses a fire risk because it's not made of metal, not fire-rated and not of solid-core construction. Recommend having a qualified contractor replace this door with a fire-rated door.
26) The garage vehicle door doesn't appear to "auto-reverse". The door should reverse when closing and when it either strikes something or when something passes through a photo sensor at the base of the door. This is a safety hazard, especially for small children. Recommend having a qualified garage door contractor evaluate and repair as necessary.
27) Rust / water stains noted at garage - indicates water penetration under garage door. Have an apron or lip added where the driveway meets the garage door to channel water away from garage.
28) Window(s) stuck shut and can't open under normal pressure. Recommend repairing window(s) so they open easily.

Photo 6  
 
29) Noted minor cracks in the garage floor, appear to be cosmetic, no need to repair at this time.
 


Basement or Lower Level Return to table of contents  
Inspection method: Traversed
Basement interior: Partially Finished, some areas blocked from view by sheetrock, paneling, carpeting, etc.
Insulation material noted in basement / crawlspace: None noted
Vapor barrier noted: No
Pier or support post material: Wood, Appears serviceable
Beam material: Solid wood, Appears serviceable
Probed areas of main beam and support posts (if made of wood) for rot: No rot or damage noted
Floor framing: Wood joists, 2x8
Any significant damage to the framing noted: No
Visible portions of basement / crawlspace floor: Concrete, Covered with carpet, Covered with tile
Interior foundation walls were made of: Cement
Amount of foundation wall exposed and able to be inspected: Some of the foundation had at least several inches exposed
Water Penetration: None Noted. No stains on carpet, walls, or stored items to indicate water penetration to the home.
Dampness: Dehumidifier noted
Ventilation noted: Windows
Windows made of: Wood
Sump pump noted: None noted
Basement Egress: Direct walkout
30) No insulation or vapor barrier noted in basement, need to add to increase energy efficiency and reduce moisture penetration into living space.
31) Minor cracks and deterioration present in foundation. These don't appear to be a structural concern, but recommend sealing them to prevent water and insect infiltration.
 


Crawl Space Return to table of contents  
Inspection method: Traversed
Crawl space under: Rear of home
Location of insulation (if observed): Ceiling
Insulation material noted in basement / crawlspace: Fiberglass roll or batt
Estimated "R" value of insulation: R22
Pier or support post material: Bearing wall
Beam material: Solid wood
Probed areas of main beam and support posts (if made of wood) for rot: No rot or damage noted
Visible portions of basement / crawlspace floor: Dirt
Floor framing: Wood joists, 2x8
Any significant damage to the framing noted: No
Vapor barrier present: No
Foundation walls visible: Yes
Interior foundation walls were made of: Cement
Water Penetration: None Noted
Dampness: Feels damp, Smells damp, Efflorescence noted (mineral deposits on walls or floors from water seepage)
Ventilation noted: None Noted
Windows made of: None Noted
Floor drains noted in basement / crawlspace: None Noted
32) Portions of the basement or crawlspace were missing a vapor barrier. Needs to be added to decrease moisture in the home. Contact ventilation / insulation contractor for installation. More insulation should also be added in this area.
33) Need to remove debris from the crawlspace. Wood scraps attract insects.
 


Electric Service Return to table of contents  
Apparent service cable size: 200 Amps
Primary service type: Underground
Service voltage (volts): 110-220
Service conductor material: Aluminum
Meter location: Exterior at garage
Meter Ratings: 240 Volts, 200 Class, 3 Wire
Location of main service panel: Garage
Location of main disconnect(s): Breaker(s) or fuses inside of main panel
Main disconnect rating (amps): 200
Primary service overload protection type: Circuit breakers
Main electrical panel rating: 200 Amps
Branch circuit wiring type: Armored cable
Branch wiring observed in main panel: Copper
Electrical grounding observed through: Exterior ground rod
Size and number of 110-120 volt electrical circuits noted in panel: (15) 15AMP, (10) 20AMP
Size and number of 220-240 volt electrical circuits noted in panel: (3) 30AMP, (1) 50AMP, (1) 60AMP
Location of electrical sub panel(s): None noted
34) Inadequate clearance exists to the main service panel. It is blocked by shelving in front of it. Recommend having a qualified, licensed electrician make modifications as necessary so:

  • An area 3" wide by 3' deep exists in front of the panel
  • The panel is at least 5 1/2 feet above the floor
  • There's at least 6'3" of headroom
  • The wall below the panel is clear to the floor
  • 35) One or more circuit breakers are "double tapped", where 2 or more wires are clamped in a circuit breaker terminal, and the circuit breaker is only designed for 1 wire. This is a safety hazard since wires may loosen and cause arcing, sparking and fires. Recommend having a qualified, licensed electrician evaluate and repair.
    36) Does not appear to be any room for expansion (room for additional circuits or breakers) in the main panel. This may necessitate adding a sub-panel, special circuit breakers, or replacing the main panel should you wish to put additional circuits in the home.
     


    Heating and Air Conditioning Return to table of contents  
    Heating system energy source: Oil
    Heat system type: Forced hot water
    Air supplied to furnace / boiler from: Exterior
    Oil or Gas entry location: Rear
    Location of fuel shut-off: At the furnace, On the oil line
    Fuel leaks noted at time of inspection: No
    Tags or labels indicating annual servicing of heating system visible: Yes
    Brand & model of furnace / boiler: Peerless
    Apparent stage of life for furnace / boiler: Appears newer
    Boiler Leaks: None noted
    Distribution system: Copper pipe, Baseboard, Most of the heating pipes were not seen
    Location of auto-safety shutoff device(s): On the oil line
    Location of emergency shut-off switch for heating system: Switch is outside of boiler room on wall
    Location of Oil Tank: Basement
    Location of oil filter (service annually): At tank
    Evidence of a buried oil tank noted: No
    Location of air filter, if noted: None noted
    Flue pipe pitches up toward chimney or wall for safety: Yes
    Flue pipes and joints secure: Yes
    Pressure Relief Valve (safety valve) noted on boiler: Yes
    Humidifier noted on system?: No
    Location(s) of additional heating systems: None noted
    Number of zones noted: 3
    Location of thermostat(s): Living room, dining room, hallway
    Boiler / Furnace came on when thermostat was turned on: Yes
    Heat felt in all rooms that have a heat source?: Yes
    Heat in use during the inspection: No
    Heat missing from the following rooms: None
    No visible source of heat was seen in the following rooms: Basement laundry room
    Central Air Conditioning type: Electric Compressor
    Brand name on compressor: Trane
    Brand name on air handler: Trane
    Apparent age of cooling system: Newer
    Tested central cooling system: In use at time of inspection, interior of house was cool
    When air conditioning system was turned on the house seemed to cool: Already in use at time of inspection, house was cool
    Cooling was missing from the following rooms: Working in all rooms
    Insulation noted on cooling ducts: Yes
    Individual room air conditioning units observed: No
    37) Boiler pipes corroded, slight leaking at the time of inspection. Contact licensed plumber or heating contractor for repair.

    Photo 20  
    Rust, small leak at pipe above boiler
     
    38) System appears to need cleaning and yearly maintenance, last service date was last year according to the tags on the system. Have oil systems serviced on a yearly basis. Call oil company for maintenance.
    39) Boiler, central cooling system all appear to be newer and in good condition. Safety valves and secure flue fittings noted.

    Photo 19  
     
     


    Well Return to table of contents  
    Location of Well Head: Front yard
    Location of well equipment: Basement
    Location of tank shut off valve: Basement
    Well water treatment equipment noted: Yes
    40) The well casing outdoors is less than 12" above the ground. Recommend grading soil so there's at least 12" from the top of the well casing to the ground to reduce the chance of contaminants entering the well. The cap to the well is not fastened securely and should be repaired to limit access.
    41) Noted lots of condensation on the pipes around the well tank and equipment. Tank and pipes need to be insulated to prevent condensation and water pooling on the floor. This adds moisture to the inside of home, increasing risk of mold / mildew. Add insulation as needed.

    Photo 17  
    Add insulation to pipes and well tank.
     
    42) The cycle time of the well pump is too short. This indicates that the pressure tank may be waterlogged. If the tank has a bladder it may be defective. The tank may need recharging or it may need replacing. Recommend having this system evaluated by a qualified well contractor and repaired as necessary.
     


    Water Heater Return to table of contents  
    Type: Tank
    Brand and model of hot water heater: Peerless
    Estimated Age of Water Heater: Newer
    Energy source: Oil
    Capacity (in gallons) per label: 50
    Temperature - pressure relief valve with extension noted: Yes
    Automatic safety shut-off device(s) noted on unit: Yes
    After running the hot water for at least 20 minutes, the water temperature was: Hot
    Hot water faucets were random tested throughout the house and: Hot water was received at each faucet
    Hot water heater flue type: Flue pipe vents into chimney
    Flue pipe pitches up toward chimney or wall for safety: Yes
    43) Water heater newer, good condition.

    Photo 21  
     
     


    Plumbing and Laundry Return to table of contents  
    Location of well pipes entering home: Front
    Water entry pipes appear to be made of: Plastic
    Type of water service is stated by Realtor / real estate listing to be: Private
    Location of water meter: None noted
    Location of main water shut-off valve: At tank, basement front
    Interior water supply pipes made of: Copper
    Insulation noted on supply pipes: No
    Tested pressure by opening multiple fixtures and flushing toilet to stress the system. Noted the following: No Decrease in Flow
    Kitchen sink made of: Stainless Steel
    Ran water at kitchen sink: No leaks noted
    Disposal brand and horsepower: None noted - do NOT add to a house with a septic system.
    Sewage disposal system has not been inspected but is reported by Realtor / real estate listing to be: Public
    Waste ejectors noted?: No
    Were plumbing vent pipes observed extending through roof: Yes
    Vent pipe material: Plastic
    Waste pipe material: Plastic, Cast iron, Copper
    Location of drain line: Rear of house
    Waste cleanouts observed?: Yes
    Location of laundry area: Basement
    Washer Manufacturer: Maytag
    Age of washer appears to be: Older
    Washer discharges to: Drain pipe
    Turned washer on: Washer advanced through cycles, heard water come in, splash, spin and pump out
    Dryer Brand: Maytag
    Age of dryer appears to be: Older
    Dryer powered by: Electric
    Dryer vented to: Exterior
    Tested dryer: Heard dryer spin and felt it warm up
    44) Steel hangers are used to support copper water supply pipes. This contact between dissimilar metals causes corrosion. Recommend replacing the steel hangars with copper hangars that won't cause corrosion.
    45) Non-insulated supply pipes were noted in the crawlspace or basement. Recommend insulating the pipes. This will A) help prevent any condensation forming on the pipes and decrease resulting moisture B) help keep the pipes from freezing during a cold spell , and C) increase energy efficiency.
    46) Caulking at kitchen sink missing or deteriorated, need to re-caulk around sink to prevent water penetration to the surrounding materials.
    47) Recommend you replace the rubber water supply hoses at the washer with steel braided hoses. Rubber hoses will deteriorate over time and burst under pressure, causing flooding.

    Photo 18  
     
    48) Washer and dryer appear to be older or past their useful life, need to budget for replacements as these may not last much longer.
     


    Fireplaces and Woodstoves Return to table of contents  
    Number of fireplaces and woodstoves noted: 1
    Location(s) of fireplace(s): Basement family room
    Fireplace type(s): Masonry
    Chimney type(s): Masonry
    Attempted to open damper: Opened and closed, appeared to operate correctly
    Looking past the damper opening was a flue liner visible: Yes
    Air supply from: Interior
    Opened fireplace damper, looked up chimney from the interior: Saw daylight, chimney appears unobstructed
    49) Fireplace hearth is less than 18" deep. This is a fire hazard. Recommend installing a non-combustible hearth pad or extending hearth to at least 18" deep. A significant amount of creosote (1/8" or more) visible in fireplace flue. Recommend cleaning by a qualified chimney service contractor.
    50) Fireplace mantle is loose or not attached to the fireplace, needs correction.
    51) One or more firebricks or refractory panels in the fireplace (the fireproof panels lining the fireplace walls) are cracked and need repairing. Recommend patching cracks with a high temperature resistant refractory mortar or sealant available at hardware stores. Recommend monitoring this area in the future. This type of repair will likely need annual maintenance.
     


    Basement Bathroom Return to table of contents  
    Location of bathroom: Basement rear
    Type of bathroom: Partial, no tub or shower
    Number of sinks: 1
    Sinks attached securely: Yes
    Bathroom ventilation noted: Window
    Received hot and cold water at sink, shower or bath: Yes
    Flushed toilet(s): Working
    Floor: Ceramic tile
    Ground fault interrupt circuit(s) noted: Yes, tested and working at time of inspection
    52) Cracked, loose, or broken tiles were noted in the bathroom(s). Contact a tile contractor for repair.
    53) Sink stopper missing or broken, need to add or repair so it opens and closes correctly, or have it have corrected by a licensed plumber.
    54) Bathroom door does not shut, latch, or lock correctly and needs repair.
     


    Hallway Bathroom Return to table of contents  
    Location of bathroom: 2nd floor hall
    Type of bathroom: Full
    Type of fixtures: Tub with shower
    Number of sinks: 1
    Sinks attached securely: No
    Bathroom ventilation noted: Window, None Noted
    Received hot and cold water at sink, shower or bath: Yes
    Flushed toilet(s): Not working, need repair
    Shower / tub surround made of: Tile
    Floor: Ceramic tile
    Ground fault interrupt circuit(s) noted: Yes, tested and working at time of inspection
    55) This bathroom does not have an exhaust fan installed. Even if a window that opens exists, it may not provide adequate ventilation, especially during cold weather when the window is less likely to be opened. Recommend having a qualified contractor install an exhaust fan, duct and vent cap as per standard building practices in bathrooms with showers where missing. Fan should be vented to the exterior.
    56) Noted leak at toilet, have repaired by a licensed plumber.
    57) Bathroom sink not secure, needs to be fastened to the wall.
    58) Area around sink needs to be re-caulked to prevent water damage, have it corrected by a handyman.
    59) Drip noted at the shower spout, needs repair.

    Photo 24  
     
    60) Towel bar(s) loose, need tightening.
    61) Bathroom walls and ceiling need to be repainted.
     


    Master Bathroom Return to table of contents  
    Location of bathroom: Master bedroom
    Type of bathroom: Full
    Type of fixtures: Tub with shower
    Number of sinks: 1
    Sinks attached securely: Yes
    Bathroom ventilation noted: Window, Vent to interior, needs to be corrected to vent to the exterior
    Received hot and cold water at sink, shower or bath: Yes
    Flushed toilet(s): Working
    Shower / tub surround made of: Tile
    Floor: Ceramic tile
    Ground fault interrupt circuit(s) noted: None noted, need to add for safety
    62) Add ground fault interrupt outlet for safety

    Photo 25  
     
    63) After examination it was determined that the bathroom vent exhausts to the attic. The moist air from the bathroom should always discharge to the exterior of the home and not into the attic, roof soffits, interior rooms, etc. Have a contractor examine and correct this so the vent fan is ducted completely to the outside of the home.
    64) Cracked tile noted on floor, needs repair.
     


    Kitchen and Interior Rooms Return to table of contents  
    Security system noted: No
    Was a smoke detector noted in each bedroom and hallway: No, need to add for safety
    Smoke detectors were tested by: Spraying with canned smoke
    Were carbon monoxide detectors noted: No
    Brand of refrigerator: Kenmore
    Age of refrigerator appears to be: Mid-life
    Options noted on refrigerator: Ice maker
    Operated refrigerator: Items in cooling section felt cool, freezer section felt frozen
    Brand of range: Kenmore
    Type of Range: Electric
    Apparent age of range: Mid-life
    Operated range: One or more burners did not operate
    Oven is: Part of the stove / range unit
    Oven Type: Electric
    Apparent age of oven: Mid-life
    Operated oven (self-cleaning option, if present, is not operated): Bake and broil came on and gave heat
    Ventilation made by: Nutone
    Range hood vents: To the exterior
    Operated range hood / vent: Appears to be working
    Brand of dishwasher: GE
    Estimated age of dishwasher: Newer to mid-life
    Operated dishwasher: Heard water come in, splash, pump out, appears to be working. Leak noted.
    Microwave made by: GE
    Age of built-in microwave: Newer
    Operated Microwave (heated wet paper towel or cup of water): Heated up, appears to be working
    Kitchen cabinets made of: Wood
    Kitchen counters appear to be made of: Granite
    Kitchen floor appears to be made of: Tile
    Random tested electrical outlets and found: No defects noted
    General condition of the interior rooms: Fair - some work will be needed to repair small cracks, holes and nail pops
    Interior ceilings appear to be made of: Sheetrock
    Interior walls appear to be made of: Sheetrock
    Wall insulation: Fiberglass
    Estimated "R" value of insulation: R32
    Most of the trim appears to be made of: Painted wood
    Interior floors consist of: Wood, Tile, Wall to wall carpet
    Trip hazards noted: None noted
    When floors were bounced on noticed: A normal amount of bounce
    Door types: Wood
    Types of windows: Double Hung
    Random tested a sampling of windows and found: Some windows do not open or close under normal pressure
    "Fogged" window(s) noted (leaking seal between glass panes):
    Skylights: Fixed type
    Stairways: Railings on stairs loose, needs repair
    65) An insufficient number of smoke detectors are installed. Recommend installing additional smoke detectors as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information on smoke detectors visit http://www.cpsc.gov/cpscpub/pubs/5077.html
    66) No carbon monoxide detectors noted, add at least one for safety.
    67) Noted missing faceplate(s) on interior electrical outlets and/or light switches. Need to be added for safety.
    68) Ground Fault Circuit interrupt (GFCI) outlets not noted in the kitchen. Needs to be added for safety. Recommend having a licensed electrician add outlets as needed.

    Photo 22  
    No GFCI outlets are installed in the kitchen, install for safety.
     
    69) Railings are loose and/or wobbly at the front stairs. Recommend having a qualified contractor repair or replace railings as necessary so they're securely attached
    70) Glass in window(s) broken. Many windows do not open, stuck shut. Some window counter-balances do not work (windows do not stay open). All windows older, single paned non-insulated glass and most in disrepair. Recommend replacing the windows for ease of use and to increase energy efficiency.

    Photo 23  
    Dining room windows do not open, glass broken.
     
    71) One or more burners on the range do not light or operate correctly. Have appliance service person evaluate unit, repair or adjust as needed.
    72) The doorbell appeared to be inoperable at the time of inspection. Recommend that an electrician evaluate and repair as necessary.
    73) Nail pops, cracks, and / or tape marks noted in the ceiling and walls, mostly in the living room area. Cosmetic concern only, repair as needed.
    74) Small leak at dishwasher needs repair.

    Photo 27  
     
    75) Hole noted in wall at rear bedroom, needs repair. Appears to come from recent installation of electrical wiring for central cooling system.

    Photo 26  
     
    76) Kitchen cabinets and drawers need adjustment to open and close correctly.
     


    Attic Return to table of contents  
    Attic access: Pull down stairs
    Inspection method: Traversed
    Attic flooring: Some flooring, mostly unfloored
    Attic floor framing size: 2x6 Wood
    Roof Framing: Rafters, 2x6 Wood
    Roof Decking: Plywood
    Were plumbing vent pipes observed in the attic extending through the roof: Yes
    Water stains observed in attic: No
    Water observed in attic: No
    Ventilation noted from inside attic: Gable Vent, Add more ventilation to the attic to prolong the life of the roof and to decrease the possibility of ice dams in the winter
    Whole house fan noted: No
    Attic fan noted: Yes
    Tested attic ventilation fan: Appears to be working and in serviceable condition
    Insulation material: Fiberglass roll or batt
    Insulation location(s): Floor
    Vapor barrier noted: Yes
    Insulation estimated R value: R22
    Insulation depth: 3"
    77) Recessed lights noted in attic floor close to or touching insulation. I did not find a label stating that they are safe to be in contact with insulation ("IC Rated"). This is a possible fire hazard - the light fixtures should be upgraded to IC fixtures that are safe for insulation contact OR the insulation should be pulled back so there is at least a few inches clearance around each fixture to prevent them from overheating. Please note that should you pull back the insulation from the fixtures this will negate much of the insulating value in that part of the ceiling, gaps will exist that will allow hot and cold air to flow from the attic to the interior and vice versa.
    78) Based upon conditions noted you should add more ventilation in the attic.
    79) There does not appear to be enough insulation in the attic. The Department of Energy recommends R-49 insulation for the attic in this part of the country. Recommend adding more insulation and / or vapor barriers to the area to increase energy efficiency, reduce air flow, block moisture and help prevent ice dams on the roof.
    80) Exhaust fan duct from master bath terminates in attic. Should be corrected so it vents to the exterior of the home. Recommend having a contractor install a vent cap designed for this duct that exits to the exterior, and securely attaching the duct to the cap so 100% of the exhaust fan air exits the attic.
    81) Loose screen noted on gable vent needs repair.
     
    This inspection meets or exceeds the Standards of Practice for the American Society of Home Inspectors (ASHI) and the National Association of Certified Home Inspectors (NACHI). It is intended as a general guide to help you make an evaluation as to the overall condition of the home. It is not intended to place a value on the home nor make any representation as to the advisability of purchase. It is not a guarantee or warranty. It is not an insurance policy.


    This inspection report is not a compliance inspection for any government codes or regulations, nor as a property or land survey.